PPS Docs

Intake Pressure Settings

Intake pressure settings monitor the pressure feeding the station inlet. The intake source may be a gravity-fed tank or pond, or the discharge from another station (image 1.1).

1.1 Intake pressure settings

Low intake fault limit and delay

This feature protects pumps by monitoring intake pressure to ensure adequate water supply (image 1.2). It uses two parameters:

If intake pressure falls below the fault limit, the delay timer starts. If the condition persists until the timer elapses, the station faults on low intake pressure to protect the pumps. If intake pressure recovers before the delay expires, the timer resets and normal operation continues.  

1.2 Low intake fault limit and delay

Low intake restart trials and restart delay

This feature limits how many times the station may fault and automatically restart for low intake pressure (image 1.3).

Restart conditions:

If the station exhausts the allowed restart trials, any subsequent low-intake fault will remain latched and require personnel intervention to investigate and reset.

1.3 Low intake restarts and delay

Intake PSI min (4mA) scale value and max (20mA) scale value

The PSI Min and Max scale values define the pressure range corresponding to the intake transmitter output (image 1.4). Enter the pressure that corresponds to the transmitter’s 4 mA output as the Min (4 mA) scale value, and the pressure that corresponds to the 20 mA output as the Max (20 mA) scale value. These adjustable ranges allow replacement with a transmitter that has a different span without requiring PLC reprogramming.

1.4 Transmitter scaling

Current Intake PSI 

This value displays the live pressure reported by the intake transmitter to the PLC (image 1.5).

1.5 Current PSI

Intake PID trim mode

This selectable mode reduces pump speeds as intake pressure falls to extend run time when the station is nearing low-intake conditions (image 1.6). Enable PID Trim when a station is repeatedly faulting for low intake pressure so the pumps can continue supplying flow longer as intake pressure declines.

1.6 PID trim settings

Trim min and trim start

Trim Start and Trim Min define the level-based scaling the PLC uses to compute a reduced discharge setpoint (image 1.7):

Between Trim Start and Trim Min the PLC progressively lowers the discharge setpoint to reduce pump speed and extend available run time.

1.7 trim min and start

When PID Trim is active, the PLC progressively lowers the discharge pressure setpoint to compensate for falling intake pressure. The setpoint continues to reduce as intake pressure declines until it reaches the configured Minimum System Setpoint (image 1.8).

Minimum System Setpoint

1.8 Min system setpoint

PID Filter Delay

The PID Filter Delay defines the interval between successive PID adjustments (image 1.9). A longer delay slows the station’s response to changing intake pressure, while a shorter delay yields more frequent setpoint updates and faster reaction to level changes.

1.9 PID filter delay

Other Pressure Transmitters